Arc Flash Kit - Cat 4
In Stock


$1,122.45
-
+

Description

  • KELTEK Arc Flash Protection Hood - Royal Indura® Ultra Soft® 13oz.over 7oz. w/ Arc Shield 100 cal/cm². 35% Light Transmission. Medium green. Dual pane. Anti-fog 

  • KELTEK Arc Flash Protection Jacket - Royal Indura® Ultra Soft® 13oz over 7oz. ATPV = 51.5 cal/cm². FR hook and loop closure, adjustable cuff for snug fit, double layer stand up collar

  • KELTEK Arc Flash Protection Pants - Royal Indura® Ultra Soft® 13oz. over 7oz. ATPV = 51.5 cal/cm². Button closure w/ FR hook and loop fly, adjustable waist and cuff for snug fit 

  • Insulating Rubber Gloves - Class 2 Type 1, Black, 14’’ long, ANSI / ASTM D120, EN60903 

  • Leather Protector Gloves - 12’’ cowhide glove designed for use with Class 2 Rubber Glove. Always wear over Rubber Insulating Gloves to provide protection against cuts, abrasions and punctures

  • Safety Glasses - Clear lens, anti-fogging, anti-scratch and anti-static w/ 99.9% UV protection. Glasses meet ANSI Z87.1, 2003, CSA-Z94.3 standards.

  • KELTEK Canvas Glove Protector Bags - Constructed of heavy duty canvas and double snap closure

  • KELTEK Canvas Arc Shield Protector Bags - Constructed of heavy duty canvas. Drawstring closure, helps preserve the quality of your Arc Shield

  • KELTEK Arc Flash Protection Kit Storage Bag - Nylon cordura 30’’ x 14’’ x 13’’ c/w mesh pocket with zipper closure. Yellow reflective lettering “Arc Flash Protection”. Custom lettering available

Specification

Safety Specs
PPE Category (HRC): Cat 4
ATPV: 51 Cal/cm2
Fabric Specs
Fabric Weight: 13oz / over 7oz

  

PPE Cat / Personal Protective Equipment Categories  /  HRC Categories

PPE is a combination of protective clothing, helmets, goggles, or other garments or equipment to protect eyes, head, breathing, and the full body from splashes, vapors, loose objects, and chemical penetration through personal clothing. The level of protection depends on the level of exposure in the working environment.

Always abide by the limits of use and minimum working distance. The following PPE categories are described by the National Fire Protection Association (NFPA) Standard 70E. The greater the electrical hazard, the higher the personal protective equipment arc rating must be to withstand an arc-flash incident. Please note that the following chart is a summary only



PPE CATEGORY 1

  1. Panelboards or other equipment rated 240 V ac and below
  2. Storage batteries, dc switchboards and other dc supply sources

 


Arc-rated clothing (minimum of 4 cal/cm2)

  • Arc-rated long sleeve shirt and pants or coverall
  • Arc-rated face shield or arc flash suit hood
  • Arc rated jacket, parka, rainwear or hard hat liner

Protective equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Heavy duty leather gloves
  • Leather footwear
  • No metal-framed eyeglasses, cell phones, or radios, jewelry, rings, keys or watches
  • Insulated hand tools
     



PPE CATEGORY 2

  1. Panelboards or other equipment rated >240 V ac to 600 V ac
  2. Other 600 V ac class (277V through 600 , nominal) equipment
  3. 600V ac class motor control centers
  4. Storage batteries, dc switchboards, and other dc supply sources
 


Arc-rated clothing (minimum of 8 cal/ cm2)

  • Arc-rated long sleeve shirt and pants or arc-rated coverall
  • Arc-rated face shield or arc flash suit hood and arc-rated balaclava
  • Arc rated jacket, parka, rainwear or hard hat liner

Protective equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Heavy duty leather gloves
  • Leather footwear
  • No metal-framed eyeglasses, cell phones, or radios, jewelry, rings, keys or watches
  • Insulated hand tools
     



PPE CATEGORY 3

  1. Storage batteries, dc switchboards, and other dc supply sources
  2. 100V dc to 250V dc, 7kA<= short circuit current <15kA
  3. 250V dc to 600V dc, 3kA<=short-circuit current<7kA
  4. Max arc duration: 2 seconds
  5. Min working distance: 18 inches
 

Arc-rated clothing (minimum of 25 cal/ cm2)

  • Arc-rated long sleeve shirt
  • Arc-rated pants
  • Arc-rated coverall
  • Arc-rated arc flash suit jacket
  • Arc-rated arc flash suit pants
  • Arc-rated arc flash suit hood
  • Arc-rated arc flash gloves
  • Arc-rated jacket, parka. rainwear or hard hat liner

Protective equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Heavy duty leather gloves
  • Leather footwear
  • No metal-framed eyeglasses, cell phones, or radios, jewelry, rings, keys or watches
  • Insulated hand tools
     



PPE CATEGORY 4

  1. 600 V class motor control centers
  2. 600 V class switchgear (with power circuit breakers or fused switches) and 600 V class switchboards
  3. NEMA E2 motor starters, 2.3kV through 7.2 kV
  4. Metal-clad switchgear, 1kV through 7.2kV
  5. Other equipment 1kV through 15kV
  6. Storage batteries, dc switchboards, and other dc supply sources

 

Arc-rated clothing (minimum of 40 cal/ cm2)

  • Arc-rated long sleeve shirt
  • Arc-rated pants
  • Arc-rated coverall
  • Arc-rated arc flash suit jacket
  • Arc-rated arc flash suit pants
  • Arc-rated arc flash suit hood
  • Arc-rated arc flash gloves
  • Arc-rated jacket, parka. rainwear or hard hat liner

Protective equipment

  • Hard hat
  • Safety glasses or goggles
  • Hearing protection (ear canal inserts)
  • Heavy duty leather gloves
  • Leather footwear
  • No metal-framed eyeglasses, cell phones, or radios, jewelry, rings, keys or watches
  • Insulated hand tools